These bolts must pass through (a) the generator mounting base, (b) the compartment floor (if a compartment is used) and (c) the supporting framework (Figure 2.3). All bolts must be long enough so that when tight, at least three threads are visible past the retaining lock nuts. Refer to Section 2.2 for the location of the generator mounting holes. Figure 2.3 - Typical Generator Restraint 1/2 INCH THICK 2.2 GENERATOR COMPARTMENTS Whether the generator set is being installed inside a compartmen
Close windows, doors and other openings in the vehicle that, if open, might permit exhaust gases to enter the vehicle. —A ESE13 A— A The generator engine gives off DEADLY carbon monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. Never operate the generator set with the vehicle inside any garage or other enclosed area. DO NOT OPERATE THE GENERATOR IF THE EXHAUST SYSTEM IS LEAKING OR HAS BEEN DAMAGED. SY
. 2.2.3 ACOUSTICS For additional noise abatement, the installer may wish to consider the following: • Using special sound-insulating materials. • Construction of a special noise abatement compartment. NOTE: Any method used to reduce noise must not adversely affect the flow of cooling and ventilating air into, or out of, the compartment. In addition to the effective use of sound insulating materials, construction of a special noise abatement compartment might be considered to reduce noise levels.
• 2.1.1 NFPA STANDARDS The following published standards booklets pertaining to standby electric systems are available form the National Fire Protection Association (NFPA), Batterymarch Park, Quincy, MA 02269: NOTE: It is essential to use the latest version of any standard to ensure correct and current information. • NFPA No. 37, STATIONARY COMBUSTION ENGINES AND GAS TURBINES. • NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR HEALTH CARE FACILITIES. • NFPA No. 220, STANDARD TYPES OF BUILDING CONS
SWAGEFORM 17 032300 1 HOLDER, FUSE 56 057593 4 MOUNT, CABLE TIE 18 022668 1 FUSE, AGC-30 57 028739 4 WRAP, TIE-4" LONG 19 076020 1 SWITCH, TOGGLE DPDT 58 061979 1 BUS, BAR 20 074074 ** ASSEM. POTTED REG. WOFIN 59* 0A2833 1 HARNESS, PANEL "PP" IP 21 067680 ** VOLTAGE REG. ASSEM. B&D 60* 0A2833A 1 HARNESS, PANEL "PP" 3P 22 075476 ** SCREW, PPHM M4-0.7 x 16MM 61 064009 1 PILOT LIGHT RED 14-V. 23 022264 ** WASHER, LOCK #8-M4 63 081988 1 DECAL-EXERCISE INFO 24 022237 1 WASHER, LOCK 3/8" 65 086381 2 C
gallons (7.6 liters) Recommended Coolant ................................Use a 50-50 mixture of ethylene glycol base. FUEL CONSUMPTION Models 004474, 004475 Using Natural Gas ..............................................441 cu. ft. per hour Using LP Gas ..................................175 cubic ft.(4.8 gal.) per hour Models 004370, 004371 Using Natural Gas ..............................................359 cu. ft. per hour Using LP Gas ..................................143 cubic ft. (4.0 gal.)
17 042558 1 KEY SQ 3/8 X 1 STEEL 18 0A5061 1 SPACER-FLEX PLATE 19 0A4989 1 PLATE, FLEX 20 052213 1 SCREW HHC M10-1.25 X 20 G8.8 21 051769 6 WASHER LOCK M12 22 049541 4 SCREW HHC M10-1.5 X 35 G8.8 23 046526 4 WASHER LOCK M10 24 045772 4 NUT HEX M10-1.5 G8 YEL CHR 25** 082130B 1 ASSY MPU SPEED SENSOR 48" 26* 087599 1 PLUG PLASTIC 3/8 CAPLUG #2 27 077043E 1 FLEX CONDUIT 1" BLACK (NOT SHOWN) 28 022131 4 WASHER FLAT 3/8 ZINC 29 072578 1 SPACER ROTOR SHAFT 30 0A7043 5 SCREW HHC M12-1.25 X 25 G8.8 31 0
51 52 Generac® Power Systems, Inc. Section 9 — Installation Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators Installation Drawing 15 & 20 kW – Drawing No. A7214-C Generac® Power Systems, Inc. 53 Section 9 — Installation Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators Installation Drawing 15 & 20 kW – Drawing No. A7214-C Air Intake Air Intake Air Outlet 54 Generac® Power Systems, Inc. Section 9 — Installation Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators Installation D
0A2803-D 24 Generac® Power Systems, Inc. Section 7 - Electrical Data Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators Electrical Schematic — Control Panel (1-Phase) — Drawing No. 0A2802-B Section 7 - Electrical Data Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators Wiring Diagram — 1.5L Gas Engine — Drawing No. 0A7176-A Generac® Power Systems, Inc. 25 (AC OUTLET) 26 Generac® Power Systems, Inc. Section 7 - Electrical Data Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators El
The NEMA 1 enclosure is intended for indoor use only. The NEMA 3R enclosure is weather proof and can be used indoors or outdoors. Follow these rules: • Install the transfer switch on a firm, sturdy supporting structure. • To prevent switch distortion, level the switch if necessary. This can be done by placing washers between the switch enclosure and the mounting surface. • Never install the switch where water or any corrosive substance might drip onto the enclosure. • Protect the switch at all t