See Fig. 1. for location of gas valve. Refer to Fig. 2 while proceeding with the following steps: Step 1 — Set room thermostat to the lowest temperature setting andset SYSTEM switchtoOFF position. Step 2 — Close the shutoff valve on the gas supply piping. Step 3 — Turn off the electrical supply to the unit and install lockout tag. Step 4 — Open the heat section access panel. Step 5 — Move ON/OFF switch on the internal main gas valve to the OFF position an Step 6 — Move ON/OFF switch on internal