NOTES: 1. Main power must be supplied from a field-supplied fused electrical service with a (factory-or field-installed) disconnect located in sight from the unit. 2. Control circuit power must be supplied from a separate source through a field-supplied disconnect. The control circuit accessory transformer may be applied to power from the main unit power supply. 3. Maximum incoming wire size for each terminal block is 500 kcmil. 4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%. 5.