The two cores are arranged for highly efficient counter current airflow. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common ECM motor. 5 speed fan operation. 120 VAC, 1.4 Amps. FILTERS Washable air filters in exhaust and supply air streams. MOUNTING THE HRV Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit. DEFROST Damper defrost system. DEHUMIDISTAT Adjustable Internal Dehumidistat. CASE Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD. CONTROLS ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode (each mode has 5 speeds). Control pad can be removed from HRV and remotely mounted. Weight 106 lbs. (48 kg) Shipping Weight 108 lbs. (49 kg) OPTIONAL MAIN CONTROLS 99-350 Lifestyle Ventilation Control 7/24 programmable ventilation, (3 wire) 20 gauge wire (min.) 100’ length 99-109 Air Sentry Air Quality Monitor designed to accept remotely mounted Control Pad, (3 wire) 20 gauge wire (min.) 100’ length 99-250 Ventilation Dehumidistat designed to accept remotely mounted Control Pad, (4 wire) 20 gauge wire (min.) 100’ length OPTIONAL TIMERS 99-104 Digital Electronic Timer - initiates high speed ventilation for 20, 40 or 60 minutes, (3 wire) 20 gauge wire (min.) 100’ length 99-101 Crank Timer - Initiates high speed ventilation for up to 60 minutes, (2 wire) 20 gauge wire (min.) 100’ length OPTIONAL ACCESSORIES 99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6” (150 mm) 99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6” (150 mm) 99-185 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh screen WARRANTY Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty. DIMENSIONS 195ECM inches (mm) METAL CLASPS Performance Net supply air flow in cfm (L/s) against external static pressure E.S.P (external static pressure) [cfm (L/s)] @ 0.1" (25 Pa) 171 (81) @ 0.2" (50 Pa) 164 (77) @ 0.3" (75 Pa) 156 (74) @ 0.4" (100 Pa) 143 (67) @ 0.5" (125 Pa) 134 (63) @ 0.6" (150 Pa) 126 (59) @ 0.7" (175 Pa) 119 (56) Max. Temperature Recovery 88% Sensible Effectiveness @ 114 cfm (54 L/s) 32°F (0°C) 88% ’Sensible Efficiency @ 114 cfm (54 L/s) 32°F (0°C) 81% ’Sensible Efficiency @ 119 cfm (56 L/s) -13°F (-25°C) 77% VAC @ 60HZ 120 WATTS / Low speed 34 WATTS / High speed 95 Amp rating 1.4 *Sensible Efficiency - thermal **Latent Efficiency - moisture Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency takes into account all power inputs All units conform to CSA and UL standards. DEFROST ! DAMPER I_T CONDENSATE DEFROST AIR DRAINS FROM INSIDE 49 " (1245) A ATTENTION The ECM motor produces a tone that some may find objectionable. We recommend the installation of the optional 99-SILENCER6 on the ‘Stale Air from Inside’ and ‘Fresh Air to Inside’ ducts. 14 3/4' (375) Date:_ Tag: _ Project:_ Engineer: _Qty:_ Contractor: Supplier:_ Quote#:_ Submitted by: nutech 511 McCormick Blvd. 270 Regency Ridge, Suite 210 London, Ontario N5W 4C8 Dayton, Ohio 45459 T (519) 457-1904 T (937) 439-6676 F (519) 457-1676 F (937) 439-6685 Email: nutech@lifebreath.com Website: ISO 9001 REGISTERED TI-195ECM NOTE: Front clearance of 25 inches (635 mm, s recommended for servicing unit....