Login:
Votes - , Average rating: ( )

User manual Bradley Smoker, model E19-120A

Manafacture: Bradley Smoker
File size: 59.89 kb
File name: 73c40fca-d538-4cc7-bc65-57c7278e2bd6.pdf

Language of manual:en

The document is loading, please wait
The document is loading, please wait

manual abstract


3 Assembly of Components ................. 4 PartsLis ............................ . 4 IMPORTANT This equipment should be inspected, tested, and recorded weekly to maintainproper operation. Main water supply to the eye wash should be “ON” at all times. This installation manual and parts list should be filed by the building owner’s maintenance department. 215-148AE Ref. G; EN 98-579 Page 1 of 4 PO. Box 309, Menomonee Falls, WI USA 53052-0309 PHONE (414) 251-6000 FAX (414) 251-5617 http:/lBradley Drench Shower Horizontal Supply Model No. E19-120A Installation Instructions Pre-Installation Information Operation The drench shower is easily activated by pulling the triangular pull rod downward, and deactivated by pushing the triangular pull rod upward. Components Showerhead: The corrosion-resistant stainless steel showerhead has a 254 mm (10”) diameter. Shower Valve: The 1” IPS stay-open valve is operated by a stainless steel pull rod with a triangle handle. Water Supply: Water supply connection is 1” BSP horizontal. Pipe and Fittings: Pipe and fittings are galvanized steel, coated with BradtectTM safety yellow. Check Contents Separate all parts from packaging and check each part with Figure 2 and the Parts List on page 4. Make sure all parts are accounted for before discarding any packaging material. If anyparts are missing, do not attempt to install your Bradley Drench Shower until you obtain themissing parts. Bradley Drench Shower Warranty Bradley Corporation warrants to commercial and institutional purchasers only each fixture free from defects inmaterial and workmanship under normal use and service upon the following terms and conditions: 1. We will replace, without charge, any part which proves to be defective within one year from the date of our invoice at our option, F.O.B. Menomonee Falls, Wisconsin. 2. This warranty does not cover installation or any other labor charge and does not apply to fixtures which have been damaged by accident, abuse or improper maintenance. 3. The repair or replacement of the defective fixtures as stated in this warranty shall constitute the sole remedy of the purchaser, and the sole liability of the Bradley Corporation under this warranty. Bradley Corporation shall not otherwise be liable under any circumstances for incidental, consequential or indirect charges causedby defects in fixtures or any delay in the repair or replacement thereof. 4. This warranty extends only to commercial and institutional purchases and does not extend to any others, including consumer, customers of commercial and institutional purchasers. 5. This warranty is in lieu of all other warranties expressed or implied, including any implied warranty of merchants ability or fitness for a particular purpose, or otherwise. 6. Bradley emergency fixtures are to be used as a supplement to first aid treatment. Bradley Corporation cannot guarantee that when used this emergency equipment will prevent serious injury or the aggravation of existing or prior injuries. No other warranties, expressed or implied are authorized, provided or guaranteed by Bradley Corporation. Bradley Corporation l 2%148AE Ref. G; EN 98-579 Bradley Drench Shower - Horizontal Supply Installation Instructions Model No. E19-120A Installation Instructions Supplies Required: l Pipe sealant l Piping to 1” BSP water supply inlet on unit l Adequate supply pipe supports l Minimum 102 mm (4”) drain to accommodate 115 liters per minute discharge for drench shower waste Step 1: Assemble drench shower NOTE: Flush the water supply line before beginning installation. 1. Assemble drench shower components as shown in Figure 2 on page 4. 2. Apply pipe sealant or tape (supplied by installer) to all male-threaded pipe joints. NOTE: Use a strap wrench around the pipes when tightening to prevent mm-ring. 3. The bottom edge of the showerhead should be 2134 mm (7-O from the floor. Step 2: Connect water supply IMPORTANT: Do not rely on Bradley’s Drench Shower to support supply piping. 1. Connect water supply piping to l-1/4 BSP inlet on unit (piping supplied by installer). Provide adequate supports (supplied by installer) for supply pipe using pipe hangers or other means. 2. Mount safety sign to wall or pipe using sign mounting hardware supplied. 3. Open water supply lines. Test for leaks and adequate water flow. Installation Instructions continued.. . I -J Figure 1 Bradley Corporation l 215148AE Ref. G; EN 98-579 Bradley Drench Shower - Horizontal Supply Model No. EM-120A Installation Instructions Assembly of Comk3onents 1” BSP SUPPLY INLET Figure 2 I i 0 4c IService Parts List ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION 1 S30-059 1 STAYaPEN BALL VALVE 4 c 180-138 2 SCREW 1A 142-002DC 1 LOCKWASHER 4D 153-235 1 ADAPTER 1c S27-278 1 1” BALL VALVE 4E 125-OOlDP 1 WASHER 1D 128-129 1 HANDLE 4F 157-005 4 DIFFUSER PADS 1E 140-720 1 STOP BRAcKEl 5* S45-314 1 SIGN-MOUNTING HARDWARE 2 113-005LKE 1 PIPE 1” IPS 8 12&158A 1 PULL ROD - 809m...

Reviews



Your review
Your name:
Please, enter two numbers from picture:
capcha





Category