manual abstract


4.2.7 IF THE MODULE DOES NOT DISPLAY THE CORRECT %PPM 1. Power cycle the unit. 2. Recalibrate the sensor. 4.2.8 IF THE DISPLAY SHOWS ‘F’ – SENSOR MISSING OR BAD SENSOR 1. Power down the unit. 2. Open the enclosure and unplug the sensor assembly from the transmitter board. 3. Plug the sensor back into the transmitter board carefully and ensure a secure fit. 4. Check all other connections. 5. Power up the unit. 4.2.9 IF THE MODULE SHOWS “***CALIBRATION REQUIRED***” 1. Calibrate the module. 4.2.10 IF THE DISPLAY SHOWS ‘H’ (OR L) THEN THE LOCAL HIGH OR LOW ALARM IS ACTIVE 4.2.11 IF THE DISPLAY SHOWS “M” – NOT CALIBRATED 1. Calibrate the module. 4.2.12 IF THE DISPLAY SHOWS “C” – CALIBRATION MODE 1. Complete calibration and exit to operating mode. 4.2.13 IF THE DISPLAY SHOWS “S” – SENTRY CONNECTION 1. Check connections with Sentry Controller 4.2.14 DIAGNOSTIC LEDS LED 1 = 1 Hz Heartbeat normal, 2 Hz Panic Error 2 = Computation process 3 = 1 Hz Heartbeat normal 4 = HART or Sentry comms activity Page: 28 Model 5100-XX-IT Toxic Gas Sensor Module 8. APPENDICES 8.1 APPENDIX A: SPECIFICATIONS Sensor: Type: Electrochemical Standard Range(1) Optional Max Range Zero Drift Repeatability Linearity Resolution Response Time(2) Accuracy Sensor Life (3) 5100-03-IT O2 5-25% Vol 0-25% Vol +/- 0.1% +/- 0.2% +/- 0.2% +/- 0.1% <10 sec. +/- 0.2% 2 years 5100-04-IT CO 0-500 PPM 1200 PPM +/- 1 PPM +/- 1 PPM +/- 1 PPM 0.5 PPM <35 sec. +/- 1 PPM 2 years 5100-05-IT H2S (5) 0-100 PPM 100 PPM +/- 0.5 PPM +/- 1 PPM +/- 1 PPM 0.1 PPM <35 sec. +/- 1 PPM 2 years 5100-06-IT Cl2 0-10.0 PPM 10.0 PPM +/- 0.5 PPM +/- 0.5 PPM +/- 0.5 PPM 0.1 PPM <60 sec. +/- 0.5 PPM 2 years 5100-08-IT ClO2 0-3.0 PPM 3.0 PPM +/- 0.5 PPM +/- 0.5 PPM +/- 0.5 PPM 0.1 PPM <60 sec. +/- 0.5 PPM 2 years 5100-10-IT SO2 0-100 PPM 100 PPM +/- 0.5 PPM +/- 1 PPM +/- 1 PPM 0.5 PPM <20 sec. +/- 0.5 PPM 2 years 5100-12-IT NO2 0-20 PPM 20.0 PPM +/- 0.5 PPM +/- 0.5 PPM +/- 0.5 PPM 0.2 PPM <35 sec. +/- 0.5 PPM 2 years 5100-21-IT HCl 0-20 PPM 20.0 PPM +/- 0.5 PPM +/- 0.5 PPM +/- 0.5 PPM 0.2 PPM <35 sec. +/- 0.5 PPM 2 years 5100-25-IT NH3 (4) 0-100 PPM 100 PPM +/- 1.0 PPM +/- 1.0 PPM +/- 1.0 PPM +/- 1 PPM <30 sec. +/- 1 PPM 1 year (6) 5100-26-IT HF (4) 0-10 PPM 10 PPM ------0.5 PPM <30 sec. +/- 1 PPM 1 year (6) (1) Optional ranges available (2) Response time to 90% full signal value for applied concentration (3) Sensor life typical for use at standard temperature and pressure with occasional exposure to gas of interest (4) Diffusion via membrane. Requires electrolyte (5) Max range, zero drift, linearity, resolution, and sensor life, have not been verified by FM Approvals. (6) Electrolyte recharge only Output: Display: Fixed and Scrolling LED Relays Option: 5 Amp, High Alarm, Low Alarm, .25 Amp Trouble all SPDT Analog Output: Analog 4-20 mA (Trouble 1.5mA, Calibration 2.5mA) Loop Resistance 800 ohm Signal Output: Sentry digital bus Analog 4-20 mA 3-wire Non-Isolated 4-wire Isolated Serial RS-485 Modbus RTU HART Input: Remote Alarm Reset: Normally open digital input Power: Power consumption: 2 watts Input voltage: 24 VDC nominal: 10-30VDC Page: 29 Model 5100-XX-IT Toxic Gas Sensor Module Operating Range: Ambient Temp (oF) Ambient Temp (oC) Relative Humidity 5100-03-IT O2 5 to 122 oF -15 to 50 oC 15 – 90% 5100-04-IT CO - 4 to 122 oF -20 to 50 oC 15 – 90% 5100-05-IT H2S (5) - 4 to 122 oF -20 to 50 oC 15 – 90% 5100-06-IT Cl2 - 4 to 122 oF -20 to 50 oC 15 – 90% 5100-08-IT ClO2 - 4 to 122 oF -20 to 50 oC 15 – 90% 5100-10-IT SO2 - 4 to 122 oF -20 to 50 oC 15 – 90% 5100-12-IT NO2 - 4 to 122 oF -20 to 50 oC 15 – 90% 5100-21-IT HCl - 4 to 122 oF -20 to 50 oC 15 – 90% 5100-25-IT NH3 (4) +14 to 113 oF -10 to 45 oC 20 – 95% 5100-26-IT HF (4) +14 to 113 oF -10 to 45 oC 20 – 95% Enclosure: Material - Aluminum: Polyester powder-coated, sand-cast, copper-free aluminum Material - Stainless Steel: 316 Stainless Steel Dimensions: (HxWxD) (differs for 5100-25-IT & 5100-26-IT) (A1) 7.9 x 5.7 x 3.9 in. (20.1 x 14.5 x 9.9 cm) (A2) 8.3 x 4.8 x 4.9 in. (21.0 x 12.2 x 12.4 cm) (S1 & S2) 7.6 x 4.4 x 4.9 in. (19.3 x 11.2 x 12.4 cm) Weight: (A1) 3.4 lb. (1.5 Kg) (A2) 5.4 lb. (2.5 Kg) (S1 & S2) 7.2 lb. (3.3 Kg) Housing: NEMA 4X, NEMA 7 Electrical Approvals: Factory Mutual (FM): Class 1, Div. I, Groups B, C, D FM Standards 3600, 3615, 3810 UL: UL Standard 508A ATEX (5100-XX-IT): II 2 G Ex d IIB+H2 T6 Gb Ta = -20oC to +50oC Performance Approvals: FM Performance Approval: FM Performance Approval (5100-05-IT) (Appendix I) SIL-2 Certified (5100-04-IT, 5100-05-IT, 5100-06-IT) CE Mark (5100-05-IT) ABS (5100-05-IT) CQST Remote Sensor Option (Appendix D): Distance between sensor and transmitter: 5100-03-IT 10 feet 5100-10-IT 15 feet 5100-04-IT 15 feet 5100-12-IT 10 feet 5100-05-IT 15 feet 5100-21-IT 10 feet 5100-06-IT 10 feet 5100-25-IT 10 feet 5100-08-IT 10 feet 5100-26-IT 10 feet Warranty: Limited Warranty: 2 years Specifications subject to change without notice Page: 30 Model 5100-XX-IT Toxic Gas Sensor Module Cross Sensitiv...

Other models in this manual:
Alarms - 5100-03-IT (2.62 mb)
Alarms - 5100-04-IT (2.62 mb)
Alarms - 5100-05-IT (2.62 mb)

Reviews



Your review
Your name:
Please, enter two numbers from picture:
capcha





Category