manual abstract


Furthermore, it can be used to actuate external devices by means of a relay output with two dry change-over Specifications Operating voltage Supply through loop voltage Current consumption approx. 1.5mA (quiescent) Contact rating 1A/30VDC or AC Ambient temperature -20°C to +70°C Dimensions L x W x H 150 x 90 x 48 (mm) Colour white Weight 240g Approval VdS G201032 Order number 249076 Order name Module lxSurv.In lxRel.Out/Apo 55000-847 contacts, via the ADM loop. In addition to the monitored input and the relay output, the module has an opto-cou-pled input for monitoring an external voltage. The address is easily selected by means of a built-in DIL switch. Status LEDs indicate the condition of input and output. The module has an integrated dual-isolator and is fitted into a plastic case. Building Safety. Building Security. © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX. +43 1 52114-27 OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED 55000-847 DBL LST EN 0804.PDF • PAGE 1...