manual abstract


Gateway 995 Series Server Rack Installation Guide
Cabinet dimensions
Your Gateway server is compatible with all cabinets (racks) that meet the
Electronic Industries Association’s (EIA’s) EIA-310-D standard.
Dimension
Measurement
Distance between vertical mounting posts
17.717 inches (450 mm) minimum
(measured from inside edges)
Distance between vertical mounting posts
18.307 inches (465 mm) minimum
(measured from mounting holes)
Distance between vertical mounting posts
19.031 inches (483.4 mm) minimum.
(measured from outside edges)
Hole sizes
Square: 0.375 inches (9.5 mm)
Round: 0.280 inches ± 0.004 inches (7.1 mm
± 0.1 mm)
Rails are designed to work with square
(preferred) or round holes, not tapped holes.
Hole spacing
Widely spaced: 0.625 inches (15.9 mm)
Closely spaced: 0.5 inches (12.7 mm)
Mounting post width
0.658 inches (16.77 mm) minimum
Clearance between mounting post and
2 inches (5.8 cm) minimum
inside front cabinet door (for server
handles)
Cabinet depth
35.4 to 39.4 inches (90 to 100 cm) minimum
Getting help
For help, call Gateway Technical Support at:

877-485-1464 (US) (24 hours a day, seven days a week, 365 days a year)

800-846-3609 (Canada and Puerto Rico) (24 hours a day, seven days a
week, 365 days a year)

800-846-1778 (TDD) (weekdays 6:00 a.m. - 8:00 p.m. Central Time,
Weekends 6:00 a.m. - 5:00 p.m. Central Time)
www.gateway.com