Allow the system to sit for approximately 20 minutes. During this period the system pressure should not rise. If the system pressure rises and stabilizes there is moisture in the system and further evacuation is needed. If the pressure continues to rise check the system for leaks. Ambients Minimum Maximum Air temperature1 10.C/50.F 37.8.C/100.F Water temperature2 4.4.C/40.F 32.2.C/90.F 1Ambient air temperature is measured at the air-cooled condenser coil inlet. 2Ambient water temperature is meas